BEKA associates Header
 
 

SERIAL TEXT DISPLAY, INTRINSICALLY SAFE, FIELD MOUNTING

 
 
BA484D Serial text display
Click for larger image

Features:

Displays text and simple graphics in a hazardous process area. Incorporating a high contrast backlit display, push buttons and two solid state outputs, this low cost operator interface is ideal for simple process control applications.

The instrument, which has ATEX, FM and IECEx intrinsic safety certification, communicates and is powered via a 2 or 3 wire system from a galvanic isolator in the safe area. To simplify hazardous area installations, the new dedicated BA201 galvanic isolator which has RS232 and RS485 safe area ports can power up to four BEKA intrinsically safe Serial Text Displays.

The text display supports Modbus, BEKA and legacy protocols and includes eleven standard screen formats which display up to four variables on each screen, some with bargraphs. If custom display formats are required, these can be constructed using the free BEKA ScreenWriter software.

A powerful Pattern Matching facility is resident in the Serial Text Display which enables the capture and display of data contained in proprietary ASCII serial strings.

Other serial text displays in our range include, intrinsically safe panel mounting model, safe area field mounting model, and safe area panel mounting model.

To select options for your application please refer to the following table.

  Model

BA484D

 

BA484D Serial text display

  Mounting

Field

  Protection

IP66

  Certification

      Europe

ATEX Group II
Category 1G
EEx ia IIC T4

      USA FM

3610 Entity CL I, II, III Div. 1
Gp A, B, C, D, E, F & G

3611 Nonincendive CL I, II, III Div. 2
Gp A, B, C, D, E, F & G

      Canada cFM

Entity CL I, II, III Div. 1
Gp A, B, C, D, E, F & G

IPA CL I, II, III Div. 2
Gp A, B, C, D, E, F & G

      International

IECEx Ex ia IIC T5

  Communications
      Interface via BA201 (other isolators may be used)

 
RS232 or RS485

      Protocol

 Modbus, BEKA & Legacy

  Operator push buttons

4

  Optional remote operator push buttons

6

  Solid state outputs

2

  Optional

      FM Certification

Yes

      cFM Certification

Yes

      ATEX & IECEx Dust Certification

Yes


  Downloads

BA484D

      Datasheet

Adobe logodownload  

      ATEX certificate

Adobe logodownload  

      FM certificate

Adobe logodownload  

      cFM certificate

Adobe logodownload  

      IECEx certificate

Adobe logodownload  

      Instruction manual

Adobe logodownload  

      Programming guide

Adobe logodownload  

      Modbus interface guide

Adobe logodownload  

      Screenwriter software & instrument simulator

File logodownload  