4/20mA Loop powered indicators, Intrinsically safe, field mounting



Ex logo

Features:

  • ATEX & IECEx intrinsic safety certification, optional FM & cFM.
  • Large non multiplexed displays, models with:
        4 digits: 34mm high
        5 digits: 29mm high + bargraph
  • IP66 GRP enclosure, separate terminal compartment
  • -40°C to +70°C operation
  • Internal calibrator
  • Root extractor and lineariser
  • Tare function
  • Optional:
        External keypad
        Backlight - may be loop or separately powered
        Alarms
        Escutcheon scale and tag labelling
        Etched stainless steel legend plate
Download logoProduct downloads

These BA304E & BA324E fourth generation intrinsically safe 4/20mA loop powered indicators have large high contrast displays with a very wide viewing angle. Operating over an extended temperature range they contain many standard features previously only available as options. Coated printed circuit boards plus extensive thermal and vibration testing provides maximum reliability supported by a three year guarantee.

No additional charge is made for factory calibration or for escutcheon scale and tag marking, however the indicators can easily be recalibrated on-site.

Other loop powered indicators in this range include:


 
 

To select the model and options for your application please refer to the following table.


Model

BA304E

BA324E

BA304E 4/20mA Loop powered indicator BA324E 4/20mA Loop powered indicator#
Mounting & Enclosure Field
Protection IP66
Display 4 digits 34mm high 5 digits 29mm high + bargraph
Certification
Europe ATEX Group II Category 1G Ex ia IIC T5 Ga -40°C ≤ Ta ≤ +70°C
International IECEx Ex ia IIC T5 Ga -40°C ≤ Ta ≤ +70°C
Optional
Alarms Yes
Backlight, which may be
loop or separately powered
Yes
External push buttons Yes
Escutcheon scale and tag labelling (no charge) Yes
Etched stainless
steel legend plate
Yes
USA FM & Canada cFM
certification
Entity IS / I, II, III / A, B, C, D, E, F, G / T5 Ta = 70°C 4X; IP66
I / 0 / AEx ia IIC / T5 Ta = 70°C
 
Non incendive NI / I / 2 / ABCD / T5 Ta = 70°C - NIFW
S / II / 2 / EFG / T5 Ta = 70°C - NIFW
S / III / T5 Ta = 70°C - NIFW
I / 2 / IIC / T5 Ta = 70°C - NIFW
Europe ATEX
Dust certification
Group II Category 1D Ex ia IIIC T80°C Da IP66, -40°C ≤ Ta ≤ +70°C
International IECEx
Dust certification
Ex ia IIIC T80°C Da IP66 -40°C ≤ Ta ≤ +70°C

 
Downloads

BA304E

BA324E

Datasheets PDF logodownload PDF logodownload
ATEX certificates PDF logodownload PDF logodownload
FM certificates PDF logodownload PDF logodownload
cFM certificates PDF logodownload PDF logodownload
IECEx certificates PDF logodownload PDF logodownload
Instruction manuals PDF logodownload PDF logodownload
Application guides AG300 PDF logodownload PDF logodownload
Declarations of Conformity PDF logodownload PDF logodownload

# Shown with optional external push buttons and backlight, separately powered.