Eight variable PROFIBUS PA display, Intrinsically safe, panel mounting



PROFIBUS PA logo

Features:

  • ATEX, FM & IECEx intrinsic safety certification, optional INMETRO.
  • Ex logoFISCO compliant
  • High contrast 86.5mm x 45mm display with backlight.
  • Up to 8 fieldbus variables
  • PROFIBUS PA protocol
  • Bus powered
  • Six optional alarm outputs
  • Push buttons may be used to send operator commands to the fieldbus host.
Download logoProduct downloads

This BA488CF-P PROFIBUS PA display instrument can display up to eight fieldbus process variables on a 86.5mm x 45mm screen.

Up to eight fieldbus variables may be displayed at the same time on one of eleven standard display screen formats, together with units of measurement and tag information. The operator can select the displayed screen via the front panel push-buttons, or these buttons may be disabled.

The fieldbus display push buttons may also be used for returning operator commands to the fieldbus host. If large industrial push buttons are required for operator inputs, external push buttons or switches may be connected to the instrument.

The fieldbus display can be supplied with six isolated alarm outputs, each of which may be linked to any of the displayed fieldbus variables. Configuration and alarm setpoints are entered via the front panel push-buttons which may be protected by a security code.

Other PROFIBUS PA displays in our range include:


 
 

To select options for your application please refer to the following table.


Model

BA488CF-P

BA488CF-P Eight variable PROFIBUS PA display
Protocol PROFIBUS PA
Mounting Panel 144 x 72mm
Protection Front IP66, rear IP20
Display High contrast 86.5mm x 45mm
with backlight, up to 8 fieldbus variables
Operator push buttons 6
Certification
Europe ATEX ATEX Group II Category 1G
Ex ia IIC T4 Ga -40°C ≤ Ta ≤ +60°C
USA FM 3610 Entity CL I Div. 1
Gp A, B, C & D T4 Ta = +60°C

3611 Nonincendive CL I Div. 2
Gp A, B, C & D T4 Ta = +60°C
International IECEx Ex ia IIC T4 Ga -40°C ≤ Ta ≤ +60°C
Optional
Connections for remote operator push buttons 6
Alarm outputs 6
Brazil INMETRO certification Ex ia IIC T4 Ga -40°C ≤ Ta ≤ +60°C

 
Downloads

BA488CF-P

Datasheet PDF logodownload
ATEX certificate PDF logodownload
FM certificate PDF logodownload
IECEx certificate PDF logodownload
INMETRO certificate PDF logodownload
PROFIBUS PA certificate PDF logodownload
Ingress certificate PDF logodownload
Instruction manual PDF logodownload
Interface guide PDF logodownload
Fieldbus display programming guide rev. 1 models PDF logodownload
Declaration of Conformity PDF logodownload
PROFIBUS PA device files ZIP logodownload
CAD files ZIP logodownload
Documentation for superseded versions Superseded documentation

 

Return to the top of this page